First, maintain the scope of management

1 , fire automatic alarm system;

2 , automatic sprinkler system;

3 , mechanical smoke exhaust system;

4 , indoor fire hydrant system;

5 , fire extinguishing equipment;

6. Safe evacuation auxiliary facilities (light evacuation indicator, emergency lighting for fire accidents)

II. Inspection of Building Fire Fighting Facilities

The inspection of firefighting facilities in buildings includes inspections, individual inspections, and joint inspections.

(I) Inspection of Building Fire Fighting Facilities

1 , the construction of fire facilities inspections should be carried out once a day.

2. The contents of the inspection of building firefighting facilities

( 1 ) Fire-fighting and power-distribution facilities: Fire-fighting power supply status.

( 2 ) Automatic fire alarm system: Appearance of fire alarm detector, fire alarm controller operation status, appearance and operation status of fire linkage controller, appearance of manual alarm button, appearance of fire alarm device.

( 3 ) Fire-fighting water supply facilities: the appearance of fire-fighting pools, the appearance of fire-fighting water tanks, the working status of fire-fighting pumps and control cabinets, the appearance and identification of water pump couplings, the state of opening and closing of pipe network control valves, and the working environment of pumping stations.

( 4 ) Fire hydrants extinguishing system: the appearance of indoor fire hydrants and the appearance of outdoor fire hydrants.

( 5 ) Automatic Sprinkler System: Appearance of Appearance, Appearance of Alarm Valve, Pressure Value of Test Equipment at the End.

( 6 ) Mechanical exhaust system: appearance of exhaust valve, appearance of natural exhaust window, working condition of exhauster.

( 7 ) Emergency lighting and evacuation signs: appearance of emergency lights, working status of emergency lights, appearance of evacuation signs, and working status of evacuation signs.

( 8 ) Fire Extinguisher: The appearance of the fire extinguisher, setting the position status.

(II) Periodic inspection of building firefighting facilities

1. The single inspection of building fire protection facilities shall be organized at least once a month by the fire safety manager and fill out the “Construction Fire Protection Facilities Periodic Inspection Record Form”. The inspection personnel and fire safety managers shall be in the “Construction Fire Fighting Facilities Periodic Inspection Record Form Sign on.

2. The contents of regular inspections of building fire protection facilities:

( 1 ) Fire-fighting power supply and distribution facilities: The power supply for the fire-fighting power equipment is the main switch and the standby power switch function.

( 2 ) Automatic fire alarm system: alarm function of alarm device, alarm display function of fire alarm detector, manual alarm button, fire alarm controller, fire display panel, linkage control and display of fire linkage control equipment. The number of inspections of the alarm function of the fire alarm detector and the manual alarm button is not less than 25 % of the total number .

( 3 ) Fire-fighting water supply facilities: fire-fighting tanks, water volume of water tanks, fire pump and pump control cabinets, start pump and main/standby pump switching functions, and pipeline valve opening/closing functions.

( 4 ) Fire hydrants extinguishing system: indoor and outdoor fire hydrants to eliminate water and pressure, fire hydrant pump button, system functions. The number of inspections is not less than 25 % of the total number .

( 5 ) Automatic Sprinkler System: The alarm valve unit discharges water, and the end test water device discharges water. The number of water discharge inspections at the end of the test equipment is the total inspection.

( 6 ) Mechanical smoke exhaust facilities: mechanical exhaust fan, exhaust valve and system functions, exhaust fan control cabinet.

( 7 ) Emergency lighting and evacuation indication signs: power supply switching and charging functions, marking correctness.

( 8 ) Fire extinguisher: Check the fire extinguisher model, pressure value and maintenance period. The number of inspections is not less than 25 % of the total number .

3 , the problems and faults found should be handled in a timely manner, on the spot can not be handled to fill in the "building fire maintenance equipment failure maintenance records", reported to the fire safety manager.

(III) Linkage Inspection of Building Fire Fighting Facilities

1. The linkage inspection of building fire fighting facilities shall be carried out at least once a year, and shall be comprehensively inspected and evaluated for the linkage control function of the building fire fighting facility system.

2. The linkage testing of building firefighting facilities is entrusted by the unit that has the qualification for firefighting inspection intermediary service, and the annual linkage inspection record is recorded in each year.    month    Before the day, they were reported to the local public security fire control agency for the record.

3. Contents of linkage inspection of building fire fighting facilities:

( 1 ) Check the power supply function of the fire-fighting and power supply facilities and the switching function of the main and standby power supplies, and check the power supply capacity.

( 2 ) Functional tests of each automatic fire alarm device, each circuit alarm system and linkage control device. Check every detector, manual alarm button no less than once every 12 months.

( 3 ) The automatic sprinkler system discharges water at the end and performs system function linkage test, water flow indicator alarm, pressure switch and hydraulic alarm bell action. Check the instrumentation on the firefighting facilities; check each end drain valve no less than once every 12 months.

( 4 ) The most unfavorable point of fire hydrant system fire hydrant water, respectively fire water tanks and fire pumps water supply. Every 12 months cumulatively checks every fire hydrant and reel no less than once.

(5) fire extinguisher for each selection, pressure and validity checks every 12 months at least once.

4. The problems and faults found should be handled in a timely manner. The “Failure Maintenance Record Form for Building Fire Fighting Facilities” should be filled out and reported to the fire safety manager.

Third, the construction of firefighting facilities maintenance and troubleshooting procedures

1. Formulate the “Maintenance and Maintenance Schedule for Building Fire Protection Facilities” based on the requirements of the environment and product maintenance of fire protection facilities, and carry out regular cleaning, maintenance and replacement. For fire-fighting equipment, pipelines and valves that are easily polluted and rust-prone to rust, they should be cleaned, rusted, and lubricated at least once every six months.

2. If it is found that there are problems and failures in the building's firefighting facilities, the personnel conducting the inspections must report to the fire safety manager and repair it in time.

IV. Management of building fire protection facility files

1 , content

The archives of construction firefighting facilities should contain basic information and dynamic management. The basic conditions include the acceptance documents and products of the building fire-fighting facilities, system operating instructions, system commissioning records, and other original technical data. The dynamic management situation includes on-duty records of construction firefighting facilities, inspection records, individual inspection records, linkage inspection records, and troubleshooting records.

2. Shelf life

( 1 ) The original technical data of the building's firefighting facilities should be kept for a long time.

( 2 ) The filing time of the "Fire Control Room Duty Record" shall not be less than 1 year.

( 3 ) The archival time of “Trouble Record of Building Fire Fighting Facilities” shall not be less than 3 years.

The information in this article comes from the Internet and was reorganized and edited by China Rescue Equipment Network.

Main material:

High manganese steel, high manganese steel quality, new composite materials, modified high manganese steel, new high manganese, high manganese steel, High manganese steel Modification.

Applicable materials
Cone crusher widely used in mining industry, metallurgical industry, building industry, road construction industry, chemical industry and silicate industry for crushing hard and medium hard rocks and ores, such as iron ore, limestone, copper ore, quartz, granite, sandstone, etc.

Mantle And Bowl Liner

Telsmith Crusher Parts,Symons Mantle And Bowl Liner,Telsmith Mantle And Bowl Liner,Mantle And Bowl Liner

Ma An Shan Shi Bo Da Jing Shen Machinery Co.,ltd , https://www.bodamachinery.com